GreenMAX Behavior List (LumaCAN 3)

CONTROL ELEMENTS:LV/DIG SWITCHOCC
SENSOR
PHOTOCELLTIME CLOCK 
BehaviorMAN
ON
MAN
OFF
AUTO
ON
VAC
OFF
PHO
ON
PHO
OFF
SCHED
ON
SCHED
OFF
Description
B1PS - P -  -  -  - B1 Auto OFF, Man ON/OFF
Lights turned ON with the switch.
Can be turned OFF with switch.
Occupancy Sensor will turn OFF upon vacancy.
B2SSPP -  -  -  - B2 Auto ON/OFF, Man ON/OFF
Lights turned ON with the Occupancy Sensor.
Can be turned OFF/ON with switch.
Occupancy sensor will turn OFF upon vacancy
B3 -  - PP -  -  -  - B3 Auto ON/OFF
 
Occupancy sensor turns lights ON/OFF
 
B4PP -  -  -  -  -  - B4 Man ON/OFF
 
Switch ON/OFF
B5 -  -  -  -  -  -  - PB5 Blink Warn Sequence
Time initiates a Blink Warn sequence.
Switch interrupts sequence and starts interval timer. Will automatically turn Off relay if interval timer reaches zero.
B6 -  -  -  -  -  - P - B6 ON
 
Turn ON at specific time.
B7 -  -  -  -  -  -  - PB7 OFF
 
Turn OFF and Relinquish control at specific time.
BehaviorMAN
ON
MAN
OFF
AUTO
ON
VAC
OFF
PHO
ON
PHO
OFF
SCHED
ON
SCHED
OFF
Description
B8 -  - SPSP -  - B8 Auto ON/OFF, Photocell OFF
Occupancy Sensor turns ON lights with occupancy. Measured light levels above Photocell trigger point turns/keeps lights OFF. Below set-point allows Occupancy Sensor control.Vacancy turns OFF lights.
B9PS - PSS -  -  B9 Auto OFF, Man ON/OFF, Photocell OFF
Switch turns ON/OFF lights. Measured light levels above Photocell trigger point turns/keeps lights OFF, Below set-point allows Switch and Occupancy Sensor control. Occupancy Sensor will turn OFF lights upon vacancy.
B10SSPPSS -  - B10 Auto ON/OFF, Man ON/OFF, Photocell ON/OFF
Occupancy Sensor turns ON lights with occupancy. Measured light levels above Photocell trigger point turns OFF or keeps lights OFF, below set-point allows Occupancy Sensor control. Switch can turn ON/OFF lights by over-riding Occupancy Sensor control. Occupancy Sensor will turn OFF lights upon vacancy.
B11PP -  - SS -  - B11 Man ON/OFF, Photocell OFF
Switch ON/OFF. Measured light levels above Photocell trigger point turns OFF or keeps lights 8 OFF, below set-point allows Switch control.
B12 -  -  -  - SPP - B12 ON, Photocell ON/OFF
Turn ON at specific time. Measured light levels above Photocell trigger point turns OFF or keeps lights OFF, below set-point allows Forced ON control.
B13 -  - P - SSP  - B13 Auto Partial ON/Auto OFF, Man ON/OFF
When Occupancy is detected, the lights will turn ON at the field-configured Partial ON Level. Press of the ON button will initiate Daylight Harvesting at Target Level. If OFF, a press of the ON button will turn ON lights at the Partial ON value. Press of the OFF button or vacancy detection will turn OFF lights.
B14 -  - SS -  -  P - B14 Auto ON/Auto Partial OFF
Turn ON at and hold specific field-configured Partial OFF level. Occupancy Sensor will turn ON lights at full when Occupancy is detected. Vacancy detection by Occuancy Sensor will return lights to Partial OFF level.
BehaviorMAN
ON
MAN
OFF
AUTO
ON
VAC
OFF
PHO
ON
PHO
OFF
SCHED
ON
SCHED
OFF
Description